MFI -SiPass Multi-Function Interface
- S54502-C154-A100
Dimensions (W x H x D)
239 × 156 × 53 (mm)
Weight
0.630 kg
Tamper contact
Opening tamper switch and removal tamper switch
Colour
White
Communication protocol
FLN Field Level Network
Power supply
20 ~ 29 V DC, 1Vpp Ripple
Power consumption
116 mA @ 24V DC: No relays activated, and no inputs connected to MFI. 183 mA @ 24V DC: All relays active, inputs double balanced. 193 mA @ 24V DC: All relays active, inputs current loop
Inputs
Up to 8 Monitored inputs are used for Door position sensor inputs and REX inputs with MFI configured in Door Controller mode. These 8 inputs can be used as general input points with MFI configured in input-output controller mode.
Relay outputs
8 relay outputs, max 30 V DC , 2A
Outputs
3 Open Collector Outputs, Max load 0.5A
Connectors
Supports maximum up to 8 OSDP Readers with OSDP V1 and OSDP V2 encryption.
Operating temperature
- 40 C ~ +55 C
Environmental class
II
Power output
12V DC, max 500mA protected by firmware controlled e-fuse Can be used to connect readers or any other load, but restricted to 500mA overall current output. 24V DC, max 1500mA protected by firmware controlled e-fuse Can be used to connect readers or any other load, but restricted to 1500mA overall current output. 24V DC, max current restricted by MFI power supply capability Can be used for powering door locks. However, it is not suggested for powering readers as there is no firmware controlled fuse to detect over current draw.